Transformer trough | automatic drainage system 4.0

Customer Case

Transformer trays

Transformer trays of transformers Ua1, Ua2 and Ua3,
Dortmund substation, Germany.

Insulating liquid: mineral oil

Destination

Use of an automatic drainage system for transformer trays with 5 ppm as the tested measured value for the oil concentration in the discharged precipitation water (general construction approval or type approval (DiBt) required).

Dortmund substation

Validation phase

For a test period of 5-6 months, three SIPP™ Nodes 500 for fully automatic dewatering, logging and continuous level control were installed on three transformer trays.

  • Pumping cycle: Continuous minimization of water levels depending on precipitation.
  • Abort discharge: oil concentration ≥ 5 ppm
  • Measurement accuracy: +/- 1 ppm
  • Measuring range: 0-20 ppm
  • Sampling frequency: Once per second

Status and process data can be retrieved from the SIPP™ Warehouse via the Internet or sent as real-time messages via e-mail or an API interface. Server location in Germany, SSL encryption and fixed IP addresses secure data transmission.

automatic drainage system, transformer tray, SIPP Node

Result

The connectivity of the three SIPP™ Nodes 500 was Ø 99.627 %. A total of approx. 10 m³ of water per transformer was pumped out in an environmentally safe and documented manner – without the need for personnel on site.

Summary:

  • No error messages or malfunctions
  • Long filter life – saturation < 30 % (filter serves as protection of the measuring instrument)
  • Long calibration intervals of the measuring cell – only 9 % consumed in 6 months
  • Water level during the whole period below the predefined critical level
  • No derivation without pump protocol takes place

The use of SIPP™ Nodes is approved throughout the Group as an automatic drainage device for transformer trays.

Connectivity

SIPP Node,
Serial no.

Connectivity
Status
OK

Warning
> 12 hrs.
Error not fixed
Warning
> 72 hrs.
Error not fixed
G4S-15119 99,632 % 100 % 0 % 0 %
G4S-15114 99,639 % 100 % 0 % 0 %
G4S-15115 99,609 % 100 % 0 % 0 %

Process data

SIPP Node,
Serial no.

Quantity
the protocols

Volume
Derived
Water
Remaining
Filter capacity
Water level below specified maximum limit
G4S-15119 9 14.1 m³ 72 % 100 %
G4S-15114 6 9.4 m³ 77 % 100 %
G4S-15115 8 13.7 m³ 73 % 100 %